Co oznacza jednostka Rack U w szafach serwerowych?

Spis treści

Stepping into a server room or even just looking at a rack can initially seem confusing. How does all that gear fit? That’s where the Rack Unit, or “U,” comes in. It’s the standard measure for vertical space in server racks. Understanding ‘U’ is key for anyone handling server hardware – it tells you exactly how much vertical room equipment is needed. It simplifies fitting everything. Stick with me, and we’ll nail down what a rack unit is, how you can figure out your own gear’s size, run through the useful conversions, and look at how those rack holes work.

Kamada Power 1U 2U 3U 4U 5U Server Rack Battery

What Does the Rack Unit U Mean?

A Rack Unit (U or RU) is basically how we measure how tall equipment is when it’s built to go into a server rack.

  • It’s a Set Height: Listen, one Rack Unit (1U) is always 1.75 inches tall. That’s the absolute core measurement everything else in the rack world is based on. (Yep, that also comes out to 44.45 mm in metric).
  • It’s Official: This isn’t just some size someone decided on randomly. This standard measurement comes from the Electronic Industries Alliance (EIA-310 standard). That’s key because it’s what guarantees gear made by different companies will physically fit into those standard racks built to the same spec.
  • It Sizes Gear: Your equipment – things like servers, network switches, batteries, you name it – all come in heights that are exact multiples of this U size (so you get 1U, 2U, 4U, and so on). They’re designed to stack up perfectly.
  • It Sizes Racks: And the racks themselves? They’re sized too, based on the total U count they can hold vertically (like those big 42U racks you see everywhere).

How to Calculate Rack Units

Do you have a device and need its U size? Use this quick method. It helps plan rack space without guessing.

KrokWhat to Do
1Measure Height: Find the device’s total vertical height. Don’t include extra bumps or handles.
2Use Inches: Convert that height to inches if needed (1 inch = 25.4 mm).
3Divide: Divide the height in inches by 1.75 (inches per U).

Formula:

U = Device Height (in inches) ÷ 1.75

Przykład:

  • A server measures 5.25 inches tall.
  • Calculation: 5.25 ÷ 1.75 = 3U.
  • It’s a 3U server.

This simple math helps confirm the device size for correct placement in your rack.

Server Rack Unit Conversion

Need to switch between U, inches, millimeters, or centimeters? These conversions are helpful.

The core factors are: 1U = 1.75 inches = 44.45 mm = 4.445 cm.

These simple conversions save time when checking specs or dimensions.

Rack U to Inches

One rack unit is always 1.75 inches.

Formula:

1U = 1.75 inches

Przykład:

  • A 3U device = 3 × 1.75 = 5.25 inches tall.

1U to Inches

Exactly 1U height is 1.75 inches.

Formula:

1U = 1.75 inches

This is the fundamental conversion you need to know.

Rack Unit to Millimeters

To convert U to millimeters, multiply the number of U’s by 44.45 mm.

Formula:

Height (mm) = U × 44.45

Przykład:

  • A 4U device = 4 × 44.45 = 177.8 mm tall.

Rack Unit to Centimeters

To convert U to centimeters, multiply the number of U’s by 4.445 cm.

Formula:

Height (cm) = U × 4.445

Przykład:

  • A 5U device = 5 × 4.445 = 22.225 cm tall.

Rack Unit Conversion Formula

Here are the core conversions:

1U = 1.75 inches = 44.45 millimeters = 4.445 centimeters

Rack U Size Chart

Rack Unit(u)RU Height(mm)RU Height(inch)RU Height(cm)
1U44.45mm1.75″4.445cm
2U88.90mm3.50″8.890cm
3U133.35mm5.25″13.335cm
4U177.80mm7.00″17.780cm
5U222.25mm8.75″22.225cm
6U266.70mm10.50″26.670cm
7U311.15mm12.25″31.115cm
8U355.60mm14.00″35.560cm
9U400.05mm15.75″40.005cm
10U444.50mm17.50″44.450cm
11U488.95mm19.25″48.895cm
12U533.40mm21.00″53.340cm
13U577.85mm22.75″57.785cm
14U622.30mm24.50″62.230cm
15U666.75mm26.25″66.675cm
16U711.20mm28.00″71.120cm
17U755.65mm29.75″75.565cm
18U800.10mm31.50″80.010cm
19U844.55mm33.25″84.455cm
20U889.00mm35.00″88.900cm
21U933.45mm36.75″93.345cm
22U977.90mm38.50″97.790cm
23U1022.35mm40.25″102.235cm
24U1066.80mm42.00″106.680cm
25U1111.25mm43.75″111.125cm
26U1155.70mm45.50″115.570cm
27U1200.15mm47.25″120.015cm
28U1244.60mm49.00″124.460cm
29U1289.05mm50.75″128.905cm
30U1333.50mm52.50″133.350cm
31U1377.95mm54.25″137.795cm
32U1422.40mm56.00″142.240cm
33U1466.85mm57.75″146.685cm
34U1511.30mm59.50″151.130cm
35U1555.75mm61.25″155.575cm
36U1600.20mm63.00″160.020cm
37U1644.65mm64.75″164.465cm
38U1689.10mm66.50″168.910cm
39U1733.55mm68.25″173.355cm
40U1778.00mm70.00″177.800cm
41U1822.45mm71.75″182.245cm
42U1866.90mm73.50″186.690cm
43U1911.35mm75.25″191.135cm
44U1955.80mm77.00″195.580cm
45U2000.25mm78.75″200.025cm
46U2044.70mm80.50″204.470cm
47U2089.15mm82.25″208.915cm
48U2133.60mm84.00″213.360cm

Rack Hole and Rack Unit Relationship

Take a real close look at the vertical rails inside any standard server rack, and you’re gonna see a bunch of holes running up and down. These aren’t random! These rack holes are exactly where you bolt your gear in, whether you’re using screws or cage nuts. And here’s the neat part: they line up perfectly with the Rack Unit system we’ve been talking about. Understanding their pattern makes working with racks much clearer.

What is a Rack Unit (U)?

Just as a quick recap: Think of a Rack Unit (U) as the standard way we measure the vertical height for equipment that goes into a server rack. One 1U space is equal to 1.75 inches (that’s about 44.45 mm).

What is a Rack Hole?

So, these rack holes are the specific spots drilled into the rack rails where you make your connections for mounting equipment. They aren’t just scattered randomly, though. The key thing is they come in specific groups along the rail, and these groups are spaced out to exactly match the standard U sizes. One of these hole groups marks out the height of one U.

How Do Rack Holes Relate to Rack Units?

  • Dla 1U of equipment, there are three holes on the rack.
  • The holes are spaced consistently:
    • Top-to-middle gap: 0.625 inches (15.875 mm)
    • Middle-to-bottom gap: 0.625 inches
    • Bottom-to-next top gap: 0.5 inches (12.7 mm)

Common Rack Unit Applications

Different gear usually comes in certain U sizes based on needs like space or cooling. Knowing these helps plan your rack.

U SizeTypical Gear You’ll See
1UNetwork switches, firewalls, small servers, patch panels. Good for saving vertical space.
2UStandard servers, storage servers, common UPS batteries. Need more internal space.
3UOlder or specialized gear like tape libraries, and dense storage. Less common for new servers.
4UBig storage arrays, GPU servers, large UPS. Need significant height.
5U+Very large systems, modular batteries, custom gear.

This gives you a quick idea of how much space different types of IT equipment usually need.

Wnioski

Getting a handle on Rack Units (U) is key to managing server racks and bateria do szafy serwerowej. Understanding U means you can pick gear that fits, plan your space right, and keep everything organized. It simplifies installation and helps maximize your vertical space efficiently

kamada power as Professional bateria do szafy serwerowej manufacturer in china, customised server rack battery according to requirements. Kontakt kamada power uzyskać wycenę.

Komentarze

Więcej blogów

Dowiedz się więcej o wiedzy i trendach w branży baterii litowych z naszego bloga.

Co oznacza jednostka Rack U w szafach serwerowych?

Wejście do serwerowni lub nawet samo spojrzenie na szafę może początkowo wydawać się mylące. Jak zmieścić cały ten sprzęt? W tym miejscu pojawia się jednostka Rack Unit, czyli "U". Jest to standardowa miara przestrzeni pionowej w szafach serwerowych. Zrozumienie "U" jest kluczowe dla każdego, kto zajmuje się sprzętem serwerowym - mówi dokładnie

Czytaj więcej "

Bateria naścienna a bateria do szafy serwerowej, która jest najlepsza dla Ciebie?

Wybór odpowiedniego magazynu energii ma kluczowe znaczenie, niezależnie od tego, czy walczysz z przerwami w dostawie prądu, wysokimi kosztami energii elektrycznej, czy też dążysz do niezależności energetycznej. Gdy już zdecydujesz się na baterię, pojawia się kluczowe rozwidlenie dróg: elegancka bateria montowana na ścianie lub funkcjonalna bateria montowana w szafie serwerowej. Która ścieżka jest odpowiednia dla Ciebie? Jako ekspert w dziedzinie baterii China Kamada Power

Czytaj więcej "

Co oznacza ESS w systemach magazynowania energii?

Co oznacza ESS w systemach magazynowania energii? Porozmawiajmy o energii. Krajobraz szybko się zmienia. Energia słoneczna i wiatrowa szybko rośnie, a nasza starsza sieć nie została zbudowana z myślą o tak dynamicznym przepływie. Amerykańskie domy i firmy potrzebują niższych rachunków i niezawodnego zasilania podczas awarii. To właśnie tutaj system magazynowania energii - ESS

Czytaj więcej "
logo kamada power

Podsumuj swoją firmę, aby odwiedzający mógł dowiedzieć się o Twojej ofercie z dowolnej strony w Twojej witrynie.

Skontaktuj się

123 Main Street
Nowy Jork, NY 10001

© 2025 Wszelkie prawa zastrzeżone.

Zapytanie

Nasz zespół odeśle najlepszą ofertę w ciągu 20 minut